CB2-B2-21-450-12C-C [Carling Technologies]

Magnetic Circuit Breaker,;
CB2-B2-21-450-12C-C
型号: CB2-B2-21-450-12C-C
厂家: Carling Technologies    Carling Technologies
描述:

Magnetic Circuit Breaker,

文件: 总26页 (文件大小:2748K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
C-  
riesSeries  
C-Se  
CIRCUIT BREAKER  
The C-Series hydraulic-magnetic circuit breakers are ideal for applications that require higher amperage and  
voltage handling capability in a smaller package. They are available in 1-6 poles, 0.02-100amps, UL Recognized  
up to 480VAC or 150VDC, UL489 Listed up to 240VAC or 125VDC, with choice of time delays, terminal  
options, actuator styles and colors. The C-Series employs a unique arc chute design which allows for higher  
interrupting capacities of up to 10,000 amps. New thermoset glass filled polyester half shell construction  
provides for increased mechanical and electrical strength. The wiping contacts, mechanical linkage with two  
step actuation, clean contacts providing high, positive contact pressure and longer contact life. Available with  
American Standard or Metric Threaded Stud terminals, or Saddle Clamp screw terminals. The optional mid-trip  
handle style actuator allows a visual indication of electrical overload with or without alarm feature.  
Product Highlights:  
Extensive list of Agency Approvals  
Typical Applications:  
Marine  
Š
Š
Š
Š
Available with Standard or Metric Stud terminals,  
Telecom/Datacom  
Military  
Renewable Energy  
Generators & Welders  
or Saddle Clamp screw terminals  
Š
Š
Optional mid-trip handle style actuator  
Unique arc chute design which allows for higher  
interrupting capacities of up to 10,000 amps  
Š
Š
Š
Š
Exclusive Rockerguard and Push-To-Reset bezel  
Š
Available with new solid color and two-color Visi-  
rocker® actuators  
Š
New thermoset glass filled polyester half shell  
construction  
Carling Technologies, Inc.  
60 Johnson Avenue, Plainville, CT 06062  
Email: sales@carlingtech.com  
Application Support: team2@carlingtech.com  
Phone: 860.793.9281 Fax: 860.793.9231  
www.carlingtech.com  
|
C-Series Circuit Breaker - General Specifications  
2
Electrical  
Maximum Voltage  
Mechanical  
Endurance  
AC, 480 WYE/277 VAC, 50/60 Hz  
(see Table A.)  
UL489: AC,240 VAC. (See Table D),  
50/60 Hz, 125 VDC  
Standard current coils: 0.100,  
0.250, 0.500, 0.750, 1.00, 2.50,  
5.00, 7.50, 10.0, 15.0, 25.0, 30.0,  
35.0, 40.0, 50.0, 60.0, 70.0, 80.0,  
90.0 and 100 amps. Other ratings  
available, see Ordering Scheme.  
10,000 ON-OFF operations @ 6 per  
minute; with rated current &  
voltage.  
Trip Free  
All C-Series circuit breakers will trip  
on overload, even when actuator is  
forcibly held in the ON position.  
The operating actuator moves  
positively to the OFF position when  
an overload causes the breaker to  
trip. With mid-trip, handle moves to  
the mid position on electrical trip of  
the circuit breaker. With mid trip  
handle with alarm switch, handle  
moves to the mid position and the  
alarm switch actuates when the  
circuit breaker is electrically  
tripped.  
Current Rating  
Trip Indication  
Standard Voltage Coils DC - 6V, 12V; AC - 120V; other  
ratings available, see Ordering  
Scheme.  
Auxiliary Switch Rating SPDT; 10.1 amps-250VAC, DC Aux.  
Switch 1.0A, 65 VDC. 0.5A,  
80VDC,1/4 HP, 125VAC,VDE & TUV  
1.0 125 VAC.  
Insulation Resistance  
Dielectric Strength  
Minimum of 100 Megohms at 500  
VDC.  
Physical  
UL, CSA: 1960 V 50/60 Hz for one  
minute between all electrically  
isolated terminals. C-Series Circuit  
Breakers comply with the 8mm  
spacing and 3750V 50/60 Hz  
dielectric requirements from  
hazardous voltage to operator  
accessible surfaces, between  
adjacent poles and from main  
circuits to auxiliary circuits per  
Publications EN 60950 and  
VDE 0805.  
Number of Poles  
1-6 poles ≤ 50A; 1-4 poles @ 51-  
70A; 1-2 poles 71-100A. UL489  
Handle: 1 pole ≤ 100A, 2 pole ≤  
50A; Rocker: 1 pole ≤ 100A.  
Internal Circuit Config. Series (with or without auxiliary  
switch, mid trip & mid trip with  
alarm switch) Shunt & Relay with  
current or voltage trip coils, Dual  
Coil, Switch Only (with or without  
aux. switch). UL489: Series (with or  
without auxiliary switch, mid-trip &  
midtrip with alarm switch).  
Resistance, Impedance Values from Line to Load Terminal -  
based on Series Trip Circuit  
Weight  
Standard Colors  
Approx.112 grams/pole ( 3.95 oz).  
Housing: Black  
RESISTANCE, IMPEDANCE VALUES  
Breaker.  
from Line to Load Terminals  
(Values Based on Series Trip Circuit Breaker)  
Environmental  
1000  
CURRENT  
(AMPS)  
TOLERANCE  
(%)  
Designed and tested in accordance with requirements of  
100  
10  
specification MIL-PRF-55629 & MIL-STD-202 as follows:  
0.10 - 5.0  
5.1 - 20.0  
20.1 - 50.0  
15  
25  
35  
Shock  
Withstands 100 Gs, 6ms sawtooth  
while carrying rated current per  
Method 213, Test Condition “I”.  
Instantaneous and ultrashort curves  
tested @ 90% of rated current.  
Withstands 0.060” excursion from  
10-55 Hz & 10 Gs 55-500 Hz, @  
rated current per Method 204C,  
Test Cond. A. Instantaneous &  
ultrashort curves tested @ 90% of  
rated current.  
Method 106D, i.e., ten 24-hour  
cycles @ +25°C to +65°C,  
80-98% RH.  
Method 101, Condition A (90-95%  
RH @ 5% NaCl Solution, 96 hrs).  
Method 107D, Condition A (five  
cycles @ -55°C to +25°C to +85°C  
to +25°C).  
O
H
M
S
1
0.1  
0.01  
Vibration  
0.001  
0.01  
0.1  
1
10  
100  
AMPERE RATING  
Pulse Tolerance Curves  
60 Hz 1/2 Cycle  
Inrush Pulse Tolerance  
50 Hz 1/2 Cycle  
Moisture Resistance  
Inrush Pulse Tolerance  
I
I
r
r
Time Delay Curves  
Time Delay Curves  
42, 44  
& 46  
22x  
10x  
42, 44  
& 46  
(50 Amps Max.)  
(50 Amps Max.)  
25x  
12x  
Time Delay Curves  
Time Delay Curves  
22, 24 (100 Amps Max.)  
26 (70 Amps Max.)  
22, 24 (100 Amps Max.)  
26 (70 Amps Max.)  
Salt Spray  
t
t
10.0  
20.0  
5.0  
8.33  
16.67  
4.165  
Time in  
Milliseconds  
Thermal Shock  
Operating Temperature -40°C to +85°C  
*Manufacturer reserves the right to change product specification without prior notice.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
C-Series Circuit Breaker - General Specifications |  
3
Electrical Tables  
Table A: Lists UL Recognized & CSA Accepted configurations and performance capabilities as a Component Supplementary  
Protector  
C-SERIES TABLE A: COMPONENT SUPPLEMENTARY PROTECTORS  
SHORT CIRCUIT CAPACITY (AMPS)  
VOLTAGE  
CURRENT RATING  
APPLICATION CODES  
UL/CSA  
CIRCUIT  
CONFIGURATION  
NOTES  
WITH BACKUP  
FUSE 1  
MAX.  
RATING  
FULL LOAD  
AMPS  
GENERAL  
PURPOSE AMPS  
WITHOUT BACKUP  
FREQUENCY PHASE  
UL  
CSA  
FUSE  
32  
48  
65  
DC  
DC  
DC  
---  
---  
---  
0.02 - 100  
110 - 150  
0.02 - 70  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
5000  
5000  
5000  
5000  
7500  
7500  
10,000  
10,000  
5000  
5000  
5000  
3000  
5000  
5000  
5000  
3500  
3000  
1000  
5000  
3500  
5000  
---  
TC1, OL1, U2  
TC1, OL1, U2  
TC1, OL1, U2  
TC1, OL1, U2  
---  
---  
TC1,2, OL1,U1 TC1,2, OL1,U1  
TC1,2, OL0,U1 TC1,2, OL0,U1  
TC1,2, OL1,U1 TC1,2, OL1,U1  
TC1,2, OL0,U1 TC1,2, OL0,U1  
TC1,2, OL1,U1 TC1,2, OL1,U1  
TC1,2, OL0,U1 TC1,2, OL0,U1  
71 -100  
0.02 - 70  
---  
---  
80  
80  
DC  
DC  
---  
---  
71 -100  
0.02 - 70  
---  
---  
Must Have Agency Code "L"  
Must Have Agency Code "L"  
71 -100  
125  
125 / 250  
250  
DC  
DC  
DC  
---  
---  
---  
0.02 - 50  
0.02 - 50  
0.02 - 50  
0.02 - 100  
0.02 - 100  
---  
---  
TC1,2,OL1,U1  
TC1,2,OL1,U1  
TC1,2,OL1,U1  
TC1, OL1, U2  
TC1,2,OL1,U1  
TC1, OL0, U3  
TC1, OL0, U3  
TC1, OL1, U2  
TC1,2,OL1,U1  
TC1,2,OL1,U1  
TC1,2,OL1,U2  
TC1, OL1, U2  
TC1,2,OL1,U1  
TC1,2,OL1,C1  
TC1, OL0, U2  
TC1,2,OL1,C1  
TC1,2,OL0,U1  
TC1,2,OL1,C1  
TC1,2,OL1,C1  
TC1,2,OL0,C1  
TC1,2,OL1,C1  
TC1,2,OL0,C1  
TC1,2,OL1,U1  
TC1,2,OL1,U1  
TC1,2,OL1,U1  
TC1, OL1, U2  
TC1,2,OL1,U1  
---  
Must Have Agency Code "L"  
---  
Must Have Agency Code "L"  
---  
Must Have Agency Code "L". 2 Pole Break Required for 250 Volts  
Per Pole Rating  
---  
---  
---  
125  
50 / 60  
1
---  
Must Have Agency Code "L"  
150  
150  
DC  
DC  
---  
---  
80 - 100  
---  
Must Have Agency Code "L"  
---  
101 - 175  
---  
---  
Must Have Agency Code "L" Parallel Pole  
SERIES  
0.02 - 100  
0.02 - 50  
51 - 100  
0.02 - 100  
0.02 - 50  
0.02 - 100  
51 - 70  
---  
---  
---  
TC1, OL1, U2  
TC1,2,OL1,U1  
TC1,2,OL1,U1  
TC1,2,OL1,U2  
TC1, OL1, U2  
TC1,2,OL1,U1  
TC1,2,OL1,C1  
TC1, OL0, U2  
TC1,2,OL1,C1  
TC1,2,OL0,U1  
TC1,2,OL1,C1  
TC1,2,OL1,C1  
TC1,2,OL0,C1  
TC1,2,OL1,C1  
TC1,2,OL0,C1  
---  
---  
2 or 3 poles breaking single phase  
2 or 3 poles breaking single phase  
2 or 3 poles breaking single phase, "L" Agency Code  
Per Pole Rating  
125 / 250  
50 / 60  
1
---  
---  
---  
---  
---  
---  
1
3
---  
---  
Must Have Agency Code "L"  
---  
5000  
---  
250  
50 / 60  
0.02 - 100  
3000  
---  
0.02 - 70  
---  
---  
0.02 - 90  
---  
5000  
---  
3 poles breaking 3 phase  
5000  
---  
Must Have Agency Code "L"  
277  
50 / 60  
50 / 60  
1
3
0.02 - 50  
0.02 - 30  
---  
5000  
5000  
5000  
5000  
5000  
---  
---  
---  
3 poles breaking 3 phase  
2 poles breaking 1 phase  
480 / 277  
31 - 50  
---  
---  
0.02 - 30  
---  
---  
480  
50 / 60  
1
31 - 50  
---  
---  
80  
DC  
---  
1
0.02 - 50  
0.02 - 50  
0.02 - 50  
0.02 - 50  
0.02 - 50  
0.02 - 50  
0.02 - 50  
0.02 - 50  
0.02 - 50  
0.02 - 50  
0.02 - 50  
0.02 - 30  
---  
7500  
3000  
3500  
3000  
3500  
3000  
---  
TC1,2, OL1,U1 TC1,2, OL1,U1  
125  
50 / 60  
---  
---  
TC1, OL1, U2  
TC1, OL1, U2  
TC1,2,OL1,U1  
TC1, OL1, U2  
TC1, OL0, U2  
TC1,2,OL1,C1  
TC1,2,OL1,C1  
TC1, OL1, U2  
TC1, OL1, U2  
TC1,2,OL1,U1  
TC1, OL1, U2  
TC1, OL0, U2  
TC1,2,OL1,C1  
TC1,2,OL1,C1  
Per Pole Rating  
---  
---  
2 or 3 poles breaking single phase  
2 or 3 poles breaking single phase  
125 / 250  
50 / 60  
1
1
3
---  
---  
DUAL COIL  
---  
---  
250  
50 / 60  
---  
---  
Per Pole Rating  
---  
5000  
5000  
---  
277  
80  
50 / 60  
DC  
1
---  
1
---  
---  
3 poles breaking 3 phase  
---  
7500  
---  
TC1,2, OL1,U1 TC1,2, OL1,U1  
277  
250  
50 / 60  
50 / 60  
---  
5000  
5000  
5000  
5000  
5000  
5000  
---  
TC1,2,OL1,C1  
TC1,2,OL1,C1  
TC1,2,OL1,C1  
TC1,2,OL0,C1  
TC1,2,OL1,C1  
TC1,2,OL0,C1  
TC1,2,OL1,C1  
TC1,2,OL1,C1  
TC1,2,OL1,C1  
TC1,2,OL0,C1  
TC1,2,OL1,C1  
TC1,2,OL0,C1  
3
---  
---  
3 poles breaking 3 phase  
3 poles breaking 3 phase  
SHUNT  
RELAY  
---  
---  
480 / 277  
480  
50 / 60  
50 / 60  
3
1
31 - 50  
---  
---  
0.02 - 30  
---  
---  
2 poles breaking 1 phase  
31 - 50  
---  
---  
80  
DC  
---  
1
0.02 - 50  
0.02 - 50  
0.02 - 50  
0.02 - 70  
---  
7500  
---  
TC1,2, OL1,U1 TC1,2, OL1,U1  
277  
250  
50 / 60  
50 / 60  
---  
5000  
5000  
---  
TC1,2,OL1,C1  
TC1,2,OL1,C1  
3
---  
---  
TC1,2,OL1,C1  
TC1,2,OL1,C1  
3 poles breaking 3 phase  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
65  
80  
DC  
DC  
---  
---  
71 -100  
---  
---  
---  
0.02 - 70  
---  
---  
---  
71 -100  
---  
---  
---  
125  
50 / 60  
50 / 60  
1
1
1
3
1
0.02 - 100  
0.02 - 100  
0.02 - 100  
0.02 - 70  
0.02 - 50  
0.02 - 30  
---  
---  
---  
SWITCH ONLY  
125 / 250  
---  
---  
---  
2 or 3 poles breaking single phase  
3 poles breaking 3 phase  
---  
---  
---  
250  
277  
50 / 60  
50 / 60  
50 / 60  
---  
---  
---  
---  
---  
---  
---  
---  
---  
480 / 277  
3
31 - 50  
---  
---  
Notes:  
1.  
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amps not to exceed 125A for 50 Amp or less  
rating and not to exceed 175 for 51 through 100 Amp rating  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
|
4
C-Series Circuit Breaker - General Specifications  
Electrical Tables  
Table B: Lists UL Recognized and CSA Accepted configurations and performance capabilities as a Manual Motor Controller.  
RELAY  
Notes:  
1
UL recognized and CSA Accepted at 480V refers to 3 & 4 pole versions used in a 3Ø, wye connected circuit or 2-pole version connected with 2 poles breaking. 1Ø and backed up with  
series fusing as stated above in note 1.  
*
Series, Shunt and Relay Trip - Voltage Coil Construction not current coils  
Table C: Lists UL Recognized, CSA Accepted, VDE and TUV Certified configurations and performance capabilities as a  
Component Supplementary Protector.  
Notes:  
1.  
2.  
General Purpose ratings for UL/CSA only.  
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amps not to exceed 125A for 50 Amp or less  
rating and not to exceed 175 for 51 through 100 Amp rating.  
Table D: Lists UL Listed (489), CSA Certified (C22.2 No. 5.1-M) configuration and performance capabilities as a Molded Case  
Circuit Breaker.  
C SERIES TABLE D : UL489 LISTED BRANCH CIRCUIT BREAKERS  
INTERRUPTING  
CAPACITY  
(AMPS)  
CURRENT  
RATING  
VOLTAGE  
FREQUENCY  
DC  
CIRCUIT  
CONFIGURATION  
CONSTRUCTION NOTES  
MAX.  
RATING  
FULL LOAD  
AMPS  
WITHOUT  
BACKUP FUSE  
PHASE  
---  
50,0001  
10,000  
Limited to 2 Poles Max from 71 - 100 Amps.  
80  
0.10 - 100  
Limited to 2 Poles Max from 71 - 100 Amps.  
125  
DC  
DC  
---  
---  
0.10 - 100  
0.10 - 50  
0.10 - 50  
51 - 70  
5,000  
5,000  
1 - 3 Poles  
125 / 250  
1 or 2 Poles (2 Poles Required for 250 Volts)  
10,000  
5,000  
1 - 3 Poles  
120  
50 / 60  
50 / 60  
1
1
SERIES  
1 - 3 Poles  
0.10 - 50  
5,000  
2 or 3 Poles. 1 Pole of a 3 Pole Unit is Neutral  
120 / 240  
100001  
5,000  
2 or 3 Poles. 1 Pole of a 3 Pole Unit is Neutral  
0.10 - 50  
0.10 - 30  
0.10 - 20  
0.10 - 20  
0.10 - 30  
240  
240  
277  
120  
50 / 60  
50 / 60  
50 / 60  
50 / 60  
1
1
1
1
1Pole  
2 Pole  
1Pole  
---  
5,000  
10,000  
10,000  
DUAL COIL  
Notes from Table D:  
1.  
Special catalog number required. Consult factory.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
C-Series Circuit Breaker - General Specifications |  
5
Electrical Tables  
Table E: Lists UL Recognized, CSA Accepted configurations and performance capabilities as Protectors, Supplementary for  
Marine Electrical and Fuel Systems (Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classified Small Craft  
Electrical Devices, Marine in accordance with ISO 8846 (Guide UZMK, File MQ1515) as Marine Supplementary Protectors.  
Table F: Lists UL Listed configurations and performance capabilities as Circuit Breakers for use in Communications Equipment  
(Guide DITT, File E189195), under UL489A.  
Agency Certifications  
Component Supplementary  
Protector under Class 3215 30,  
FIle 047848 0 000 CSA  
UL Recognized  
UL Standard 1077  
CSA Accepted  
Component Recognition Program  
as Protectors Supplementary  
(Guide CCN/QVNU2, File E75596)  
Standard C22.2 No. 235  
Switches, Industrial Control  
(Guide CCN/NRNT2, File E148683)  
Circuit Breaker Model Case  
(Class 1432 01, File 093910),  
CSA Standard C22.2 No. 5.1 - M  
UL Standard 508  
UL Standard 1500  
CSA Certified  
TUV Certified  
VDE Certified  
Protectors, Supplementary for  
Marine Electrical & Fuel Systems  
(Guide PEQZ2, File E75596)  
Ignition Protection  
EN60934, under License No.  
R72040875  
UL Listed  
UL Standard 489  
Circuit Breakers, Molded Case,  
(Guide DIVQ, File E129899)  
EN60934, VDE 0642 under File  
No. 10537  
Communications Equipment  
UL Standard 489A  
(Guide CCN/DITT, File E189195)  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
|
6
C-Series Circuit Breaker - Handle UL Recognized – Ordering Scheme  
C A 3 B 0 10 450 1 2 1 C  
8
9
10  
11  
Agency  
Approval  
1
2
3
4
5
6
7
Terminal  
Actuator  
Color  
Mounting  
Bezel/Barrier  
Series  
Actuator  
Poles  
Circuit  
Aux/Alarm  
Switch  
Frequency  
& Delay  
Current Rating  
1 SERIES  
C
7 CURRENT RATING (AMPERES)  
CODE AMPERES  
020 0.020  
025 0.025  
030 0.030  
035 0.035  
040 0.040  
045 0.045  
050 0.050  
055 0.055  
060 0.060  
065 0.065  
070 0.070  
075 0.075  
080 0.080  
085 0.085  
090 0.090  
095 0.095  
210 0.100  
215 0.150  
220 0.200  
225 0.250  
230 0.300  
235 0.350  
240 0.400  
245 0.450  
250 0.500  
255 0.550  
260 0.600  
265 0.650  
270 0.700  
275 0.750  
280 0.800  
285 0.850  
290 0.900  
295 0.950  
410 1.000  
512 1.250  
415 1.500  
517 1.750  
420 2.000  
522 2.250  
425 2.500  
527 2.750  
430 3.000  
614 14.000  
615 15.000  
616 16.000  
617 17.000  
618 18.000  
620 20.000  
622 22.000  
624 24.000  
625 25.000  
630 30.000  
635 35.000  
640 40.000  
650 50.000  
435 3.500  
440 4.000  
445 4.500  
450 5.000  
455 5.500  
460 6.000  
465 6.500  
470 7.000  
475 7.500  
480 8.000  
485 8.500  
490 9.000  
495 9.500  
610 10.000  
710 10.500  
611 11.000  
711 11.500  
612 12.000  
712 12.500  
613 13.000  
1
2 ACTUATOR  
A
B
S
T
Handle, one per pole  
Handle, one per multipole unit  
Mid-Trip Handle, one per pole  
Mid-Trip Handle, one per pole & Alarm Switch  
2
3 POLES  
1
2
One  
Two  
3
4
Three  
Four  
5
6
Five  
Six  
9
660 60.000  
9
670 70.000  
3
4
4
4,5  
4 CIRCUIT  
F
G
H
Relay Trip (Current)  
Relay Trip (Voltage)  
Dual Coil with Shunt Trip  
Voltage Coil  
Dual Coil with Relay Trip  
Voltage Coil  
9
680 80.000  
3
A
B
C
D
E
Switch Only (No Coil)  
Series Trip (Current)  
Series Trip (Voltage)  
Shunt Trip (Current)  
Shunt Trip (Voltage)  
9
685 85.000  
9
690 90.000  
9
695 95.000  
4
4
4,5  
K
9
810 100.00  
7
OR VOLTAGE COIL (NORMAL RATED VOLTAGE)  
CODE AMPERES  
5 AUXILIARY / ALARM SWITCH  
A06  
6 DC  
A32 32 DC  
A48 48 DC  
A65 65 DC  
J12 12 AC  
J18 18 AC  
J24 24 AC  
J48 48 AC  
J65  
65 AC  
0
2
3
4
without Aux Switch  
A12 12 DC  
A18 18 DC  
A24 24 DC  
K20 120 AC  
L40 240 AC  
S.P.D.T., 0.110 Q.C. Term.  
S.P.D.T., 0.139 Solder Lug  
S.P.D.T., 0.110 Q.C. Term.  
(Gold Contacts)  
6
8
9
S.P.S.T., 0.139 Solder Lug  
S.P.S.T., 0.187 Q.C. Term.  
S.P.D.T., 0.187 Q.C. Term.  
J06  
6 AC  
15  
8 TERMINAL  
10  
12  
13,15  
15  
14  
11,15  
1
2
3
4
5
Stud 10-32  
Screw 10-32  
Stud 1/4-20  
Stud M5 x 0.8  
Screw M5 x 0.8  
6
7
9
A
C
Stud M6  
11  
12  
11  
11  
0.250 Double Click Connect  
7/16” Clip Terminal  
Plug-In Stud  
6 FREQUENCY & DELAY  
3
7
03  
10  
11  
12  
14  
16  
20  
21  
22  
24  
26  
DC 50/60Hz, Switch Only  
DC Instantaneous  
DC Ultra Short  
DC Short  
DC Medium  
DC Long  
50/60Hz Instantaneous  
50/60Hz Ultra Short  
50/60Hz Short  
50/60Hz Medium  
50/60Hz Long  
30  
31  
32  
34  
36  
42  
44  
46  
52  
54  
56  
DC 50/60Hz Instantaneous  
DC 50/60Hz Ultra Short  
DC 50/60Hz Short  
DC 50/60Hz Medium  
DC 50/60Hz Long  
50/60Hz Short, Hi-Inrush  
50/60Hz Medium, Hi-Inrush  
50/60Hz Long, Hi-Inrush  
DC Short, Hi-Inrush  
DC Medium, Hi-Inrush  
DC Long, Hi-Inrush  
5/16” Clip Terminal  
16  
8
8
8
8
8
9 ACTUATOR COLOR & LEGEND  
Actuator Color  
White  
Black  
Red  
Green  
Blue  
Yellow  
Gray  
7
I-O  
A
C
F
H
K
M
P
ON-OFF  
Dual  
1
Legend Color  
Black  
White  
White  
White  
White  
Black  
Black  
Black  
B
D
G
J
2
3
4
5
6
7
8
9
L
Notes:  
N
Q
S
U
1
Actuator Code:  
A: Handle tie pin spacer(s) and retainers provided assembled with multi-pole units.  
B: Handle location as viewed from front of breaker:  
Orange  
Black (short handle)  
R
T
17  
White  
2 pole - left pole 3 pole - center pole 4 pole - two handles at center poles  
5 pole - three handles at center poles  
6 pole - four handles at center poles  
S: Handle moves to mid-position only upon electrical trip of the breaker. Available  
with circuit codes B, C, D, E, F, G, H and K.  
T: Handle moves to mid-position and alarm switch activates only upon electrical trip  
of the breaker. Available with circuit codes B & C.  
Standard multipole units have all poles identical except when specifying auxiliary  
switch and/or mixed poles. 4 pole max with VDE. 5th pole available as Series Trip with  
Voltage Coil only.  
Switch Only circuits, rated up to 50 amps and 6 poles, and only available with VDE  
Certificationꢀwhenꢀtiedꢀtoꢀaꢀprotectedꢀpoleꢀ(CircuitꢀCodeꢀB,ꢀC,ꢀDꢀorꢀH.).ꢀForꢀ.02ꢀtoꢀꢀ  
30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650.  
For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810.  
Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit  
Codes D, F, H & K available up to 50 amps maximum Current Rating.  
Consult factory for available Dual Coil options, as special catalog number is  
required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously  
on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip  
instantaneously and are rated for intermittent duty only.  
10 MOUNTING / BARRIERS  
MOUNTING STYLE  
BARRIERS  
VOLTAGE  
2
Threaded Insert  
1
6-32 x 0.195 inches  
6-32 X 0.195 inches  
6-32ꢀXꢀ0.195ꢀinchesꢀꢀ  
ISO M3 x 5mm  
ISO M3 x 5mm  
ISOꢀM3ꢀxꢀ5mmꢀꢀ  
no  
< 300  
< 300  
≥ꢀ300  
< 300  
< 300  
≥ꢀ300  
A
C
2
B
D
yes  
yesꢀꢀ  
no  
yes  
yesꢀꢀ  
3
18  
18  
4
5
Front panel Snap-In, 1.00” [25.4mm] wide bezel  
17  
E
with Handleguard  
no  
< 300  
6
Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole  
breakers, one auxiliary switch is supplied, mounted in the extreme right pole.  
Voltage coils not rated for continuous duty. Available only with delay codes 10 & 20.  
Available with Circuit Codes B & D only, and up to 50 amps maximum.  
Current Ratings 60 - 70 are available up to four poles maximum. Ratings 71 - 100  
are available up to two poles maximum.  
11 AGENCY APPROVAL  
UL Recognized, CSAAccepted  
Dꢀ VDEꢀCertified,ꢀULꢀRecognized,ꢀCSAꢀAccepted  
Eꢀ TUVꢀCertified,ꢀULꢀRecognized,ꢀCSAꢀAccepted  
C
7
8
9
Hꢀ UL489ꢀConstruction:ꢀVDEꢀCertified,ꢀULꢀRecognized,ꢀCSAꢀꢀAccepted  
10 Terminal Code 1 available to 60 amps maximum.  
11 Terminal Codes 2, 4, 5 and C available to 50 amps maximum.  
12 Terminal Codes 3, 6 & 9 available to 100 amps maximum.  
13 Terminal Code 7 available to 25 amps maximum.  
14 Terminal Code A available to 100 amps maximum.  
15 Terminal Codes 7, 9 & C are not VDE approved.  
16 No marking available. Consult factory. VDE/TUV Approval requires dual  
(I-O, ON-OFF) or I-O markings on all handles.  
I
UL Recognized STD 1077, UL Recognized 1500 (ignition protected),  
CSAAccepted  
L
UL489 Construction: UL Recognized, CSAAccepted  
Rꢀ UL489ꢀConstruction:ꢀTUVꢀCertified,ꢀULꢀRecognized,ꢀCSAꢀAccepted  
17 Single pole only.  
18 VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 - 4 poles only  
and limited to AC Delays. “General Purpose amps” not rated for “full load amps” or  
to be used in applications with a motor.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
C-Series Circuit Breaker - Handle UL489A Listed / Parallel Pole – Ordering Scheme |  
7
C A 2 P 0 D4 820 3 2 1 M T  
8
9
10  
Mounting  
11  
12  
1
2
3
4
5
6
7
Terminal  
Actuator  
Color  
Max. App. Agency  
Series  
Actuator  
Poles  
Circuit  
Aux/Alarm  
Switch  
Frequency  
& Delay  
Current Rating  
Rating  
Approval  
5
8 TERMINAL  
1 SERIES  
C
3
6
A
Stud 1/4-20  
Stud M6  
Plug-In Stud  
3
2 ACTUATOR  
A
S
T
Handle, one per pole  
Mid-Trip Handle, one per pole  
Mid-Trip, one per pole & Alarm Switch  
2
1
9 ACTUATOR COLOR  
1
LEGEND  
ON-OFF  
B
D
G
J
Dual  
Legend Color  
Black  
White  
White  
White  
White  
Black  
Black  
Black  
White  
Black  
Red  
Green  
Blue  
Yellow  
Gray  
Orange  
1
2
3
4
5
6
7
8
4
3 POLES  
One  
1
2
Two  
3
Three  
L
4 CIRCUIT  
Series Trip (parallel pole)  
N
Q
S
P
5 AUXILIARY / ALARM SWITCH  
10 MOUNTING  
0
2
3
4
without Aux Switch  
6
7
S.P.S.T., 0.139 Solder Lug  
S.P.S.T., 0.110 Q.C  
Term. (Gold Contacts)  
S.P.S.T., 0.187 Q.C. Term.  
S.P.D.T., 0.187 Q.C. Term.  
Threaded Insert  
S.P.D.T., 0.110 Q.C. Term.  
S.P.D.T., 0.139 Solder Lug  
S.P.D.T., 0.110 Q.C. Term.  
(Gold Contacts)  
1
2
6-32 x 0.195 inches  
ISO M3 x 5mm  
8
9
5
S.P.S.T., N.O., 0.110 Q.C  
Term. (Gold Contacts)  
11 MAXIMUM APPLICATION RATING  
80 DC  
M
6 FREQUENCY & DELAY  
D1 DC Ultra Short  
D2 DC Short  
D4 DC Medium  
D6 DC Long  
6
12 AGENCY APPROVAL  
A
Without Approval  
Kꢀꢀ  
T
UL489AꢀListed,ꢀVDEꢀCertifiedꢀ  
UL489A Listed  
7ꢀ  
UL489AꢀListed,ꢀTUVꢀCertified  
4
7 CURRENT RATING (AMPERES)  
CODE AMPERES  
810 100.00  
811 110.00  
812 120.00  
912 125.00  
813 130.00  
814 140.00  
815 150.00  
816 160.00  
817 170.00  
917 175.00  
818 180.00  
819 190.00  
820 200.00  
922 225.00  
825 250.00  
Notes:  
1
Handle moves to Mid-Position only upon electrical trip of C/B when Actuator S is  
specified.ꢀWhenꢀActuatorꢀCodeꢀTꢀisꢀspecified,ꢀhandleꢀmovesꢀtoꢀMidꢀPositionꢀandꢀꢀ  
Alarm Switch actuates only upon electrical trip of C/B. Code T is only available with  
Circuit Code N.  
2
3
Standard Handle colors are White, Black, Red & Yellow.  
Breakers with Terminal Codes 3 & 6 are supplied with bus bars connecting the Line  
and Load Terminals. For Terminal Code A, Line and Load Terminals must be  
connected to a copper bus bar having a minimum cross-section of 0.078 square  
inches. Terminal code A not available on the single pole unit.  
Ratings for 101 to 125 amps are available in 1-pole size.  
Ratings from 110 to 200 amps are available in 2-pole size.  
For ratings from 225-250 amps, specify 3-pole size.  
4
For ratings from 350-400 amps, specify 4-pole size.  
5
6
1 pole only available with terminal codes 3 and 6.  
Agency codes K and 7 not available with 1 pole.  
Agency code J only available with 1 pole.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
|
8
C-Series Circuit Breaker - Rocker UL489A Listed / Parallel Pole – Ordering Scheme  
C 1 2 P 0 D4 820 3 2 A M T  
8
9
10  
Mounting  
11  
12  
1
2
3
4
5
6
7
Terminal  
Actuator  
Color  
Max. App. Agency  
Series  
Actuator  
Poles  
Circuit  
Aux/Alarm  
Switch  
Frequency  
& Delay  
Current Rating  
Rating  
Approval  
3
8 TERMINAL  
1 SERIES  
C
3
6
A
Stud 1/4-20  
Stud M6  
Plug-In Stud  
1
2 ACTUATOR  
C
D
F
G
J
K
N
O
1
2
3
4
5
Curved Rocker, Two Color Visi, Indicate On, Vertical Legend  
Curved Rocker, Two Color Visi, Indicate On, Horizontal Legend  
Curved Rocker, Two Color Visi, Indicate Off, Vertical Legend  
Curved Rocker, Two Color Visi, Indicate Off, Horizontal Legend  
Curved Rocker, Single Color, Vertical Legend  
9 ACTUATOR COLOR  
LEGEND  
ON-OFF  
B
D
G
J
Dual  
Legend Color  
Black  
White  
White  
White  
White  
Black  
Black  
Black  
White  
Black  
Red  
Green  
Blue  
Yellow  
Gray  
Orange  
1
2
3
4
5
6
7
8
Curved Rocker, Single Color, Horizontal Legend  
Curved Rocker, Push To Reset, Two Color Visi, Vertical Legend  
Curved Rocker, Push To Reset, Two Color Visi, Horizontal Legend  
Flat Rocker, Two Color Visi, Vertical Legend  
Flat Rocker, Two Color Visi, Horizontal Legend  
Flat Rocker, Single Color, Vertical Legend  
L
N
Q
S
Flat Rocker, Single Color, Horizontal Legend  
Flat Rocker, Push To Reset, Two Color Visi, Vertical Legend  
Flat Rocker, Push To Reset, Two Color Visi, Horizontal Legend  
Flat Rocker, Push To Reset, Single Color, Vertical Legend  
Flat Rocker, Push To Reset, Single Color, Horizontal Legend  
6
7
8
10 MOUNTING  
ROCKER / MOUNTING INSERT STYLE  
Standard Rocker Bezel - 6-32 Inserts  
Standard Rocker Bezel - M3 Inserts  
Rocker Guard Bezel - 6-32 Inserts  
Rocker Guard Bezel - M3 Inserts  
Standard Bezel with recessed Off Side Flat Rocker - 6-32 Inserts  
Standard Bezel with recessed Off Side Flat Rocker - M3 Inserts  
Push to Reset Bezel - 6-32 Inserts  
A
B
C
D
E
F
2
3 POLES  
One  
1
2
Two  
3
Three  
4 CIRCUIT  
Series Trip (parallel pole)  
G
H
P
Push to Reset Bezel - M3 Inserts  
11 MAXIMUM APPLICATION RATING  
80 DC  
5 AUXILIARY/ALARM SWITCH  
M
0
2
3
4
without Aux Switch  
6
7
S.P.S.T., 0.139 Solder Lug  
S.P.S.T., 0.110 Q.C  
Term. (Gold Contacts)  
S.P.S.T., 0.187 Q.C. Term.  
S.P.D.T., 0.187 Q.C. Term.  
S.P.D.T., 0.110 Q.C. Term.  
S.P.D.T., 0.139 Solder Lug  
S.P.D.T., 0.110 Q.C. Term.  
(Gold Contacts)  
4
8
9
12 AGENCY APPROVAL  
A
T
7ꢀ  
Without Approval  
UL489A Listed  
UL489AꢀListed,ꢀTUVꢀCertified  
5
S.P.S.T., N.O., 0.110 Q.C  
Term. (Gold Contacts)  
Notes:  
6 FREQUENCY & DELAY  
D1 DC Ultra Short  
D2 DC Short  
D4 DC Medium  
D6 DC Long  
1
Breakers with Terminal Codes 3 & 6 are supplied with bus bars connecting the Line  
and Load Terminals. For Terminal Code A, Line and Load Terminals must be  
connected to a copper bus bar having a minimum cross-section of 0.078 square  
inches. Terminal code A not available on the single pole unit.  
Ratings for 101 to 125 amps are available in 1-pole size.  
Ratings from 110 to 200 amps are available in 2-pole size.  
For ratings from 225-250 amps, specify 3-pole size.  
2
For ratings from 350-400 amps, specify 4-pole size.  
2
3
4
1 pole only available with terminal codes 3 and 6.  
Agency codes K and 7 not available with 1 pole.  
7 CURRENT RATING (AMPERES)  
CODE AMPERES  
810 100.00  
811 110.00  
812 120.00  
912 125.00  
813 130.00  
814 140.00  
815 150.00  
816 160.00  
817 170.00  
917 175.00  
818 180.00  
819 190.00  
820 200.00  
922 225.00  
825 250.00  
Agency code J only available with 1 pole.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
C-Series Circuit Breaker - Handle UL489 Listed – Ordering Scheme |  
9
C A 3 B 0 14 450 1 2 1 K G  
8
9
10  
Mounting/  
Barriers  
11  
12  
1
2
3
4
5
6
7
Terminal  
Actuator  
Color  
Max. App. Agency  
Rating Approval  
Series  
Actuator  
Poles  
Circuit  
Aux/Alarm  
Switch  
Frequency  
& Delay  
Current Rating  
1 SERIES  
C
7 CURRENT RATING (AMPERES)  
CODE AMPERES  
210 0.100  
215 0.150  
220 0.200  
225 0.250  
230 0.300  
235 0.350  
240 0.400  
245 0.450  
250 0.500  
255 0.550  
260 0.600  
265 0.650  
270 0.700  
275 0.750  
280 0.800  
285 0.850  
290 0.900  
295 0.950  
410 1.000  
512 1.250  
415 1.500  
517 1.750  
420 2.000  
522 2.250  
425 2.500  
527 2.750  
430 3.000  
435 3.500  
440 4.000  
445 4.500  
450 5.000  
455 5.500  
460 6.000  
465 6.500  
470 7.000  
475 7.500  
480 8.000  
485 8.500  
490 9.000  
495 9.500  
610 10.000  
710 10.500  
611 11.000  
711 11.500  
612 12.000  
712 12.500  
613 13.000  
614 14.000  
615 15.000  
616 16.000  
617 17.000  
618 18.000  
620 20.000  
622 22.000  
624 24.000  
625 25.000  
630 30.000  
635 35.000  
640 40.000  
660 60.000  
670 70.000  
680 80.000  
685 85.000  
690 90.000  
695 95.000  
810 100.00  
1
2 ACTUATOR  
A
B
S
T
Handle, one per pole  
Handle, one per multipole unit  
Mid-Trip Handle, one per pole  
Mid-Trip Handle, one per pole & Alarm Switch  
2
3 POLES  
One  
1
2
Two  
3
Three  
4 CIRCUIT  
Series Trip (Current)  
B
3
5 AUXILIARY / ALARM SWITCH  
0
2
3
4
without Aux Switch  
6
8 TERMINAL  
S.P.D.T., 0.110 Q.C. Term.  
S.P.D.T., 0.139 Solder Lug  
S.P.D.T., 0.110 Q.C. Term.  
(Gold Contacts)  
6
8
9
S.P.S.T., 0.139 Solder Lug  
S.P.S.T., 0.187 Q.C. Term.  
S.P.D.T., 0.187 Q.C. Term.  
7
9
9
10  
1
2
3
4
5
Stud 10-32  
Screw 10-32  
Stud 1/4-20  
Stud M5 x 0.8  
Screw M5 x 0.8  
6
9
A
C
Stud M6  
7/16” Clip Terminal  
Plug-In Stud  
5/16” Clip Terminal  
8
9
8
8
8
6 FREQUENCY & DELAY  
11  
12  
14  
16  
21  
22  
24  
DC Ultra Short  
DC Short  
DC Medium  
26  
42  
44  
46  
52  
54  
56  
50/60Hz Long  
50/60Hz Short, Hi-Inrush  
50/60Hz Medium, Hi-Inrush  
50/60Hz Long, Hi-Inrush  
DC Short, Hi-Inrush  
DC Medium, Hi-Inrush  
DC Long, Hi-Inrush  
11  
9 ACTUATOR COLOR & LEGEND  
4
4
4
4
4
4
Actuator Color  
White  
Black  
Red  
Green  
Blue  
Yellow  
Gray  
Orange  
ON-OFF  
Dual  
Legend Color  
Black  
White  
White  
White  
White  
Black  
Black  
Black  
B
D
G
J
1
2
3
4
5
6
7
8
DC Long  
50/60Hz Ultra Short  
50/60Hz Short  
50/60Hz Medium  
L
N
Q
S
Notes:  
1
Actuator Code:  
A: Handle tie pin spacer(s) and retainers provided assembled with multi-pole units.  
B: Handle located, as viewed from front of breaker in left pole. 2 pole maximum.  
S: Handle moves to mid-position only upon electrical trip of the breaker.  
T: Handle moves to mid-position and alarm switch activates only upon electrical trip  
of the breaker.  
10 MOUNTING / BARRIERS  
MOUNTING STYLE  
12  
BARRIERS  
2
Standard multipole units have all poles identical except when specifying auxiliary  
switch and/or mixed poles.  
2 & 3 pole circuit breakers required for 120/240 VAC (Maximum application rating  
code C) applications, have all poles identical except when specifying auxiliary /  
alarmꢀswitchꢀwhichꢀisꢀnormallyꢀsuppliedꢀinꢀextremeꢀrightꢀpoleꢀperꢀfigureꢀB.ꢀTerminalꢀꢀ  
barriers are required on all multipole breakers.  
Threaded Insert  
1
2
6-32 x 0.195 inches  
ISO M3 x 5mm  
yes  
yes  
Third pole is for 120/240 VAC applications requiring neutral disconnect. The 3rd  
pole has the same construction as poles 1 & 2.  
On multi-pole breakers, one auxiliary. switch is supplied, mounted in the extreme  
right pole.  
VDE approval on auxiliary switch codes 2, 3 & 4 only.  
Auxiliary / Alarm Switch with Independent Circuit ie: separate from breaker circuit,  
only available with circuit breakers rated 50 amp maximum at 80 VDC, 125 VDC,  
and 120 VAC. Auxiliary / Alarm Switch with Dependent Circuit ie: same as circuit  
breaker, is supplied from factory with common terminal of auxiliary / alarm switch  
connected to line terminal on 120/240 and 240 VAC ratings. Circuit breakers rated  
120 VAC 50 amp maximum can be supplied with Auxiliary/Alarm switch common  
terminal connected to breaker line terminal. Consult factory for special catalog  
number.  
11 MAXIMUM APPLICATION RATING  
A
B
C
D
K
F
65 DC  
3
125 DC  
120/240 AC  
240 AC  
120 AC  
277 AC  
80 DC  
2
M
11  
12 AGENCY APPROVAL  
A
without approvals  
4
5
Available up to 50 amps maximum.  
Current ratings 71 - 100 with VDE approvals are available up to two poles  
maximum.  
Terminal Codes 9 & C are not VDE approved.  
Terminal Code 1 available to 60 amps maximum.  
Fꢀꢀ  
Gꢀ  
Jꢀꢀ  
UL489ꢀListed,ꢀCSAꢀCertifiedꢀ&ꢀVDEꢀCertified  
UL489ꢀListedꢀ&ꢀCSAꢀCertified  
6
7
8
9
UL489ꢀListed,ꢀCSAꢀCertifiedꢀ&ꢀTUVꢀCertified  
Terminal Codes 2, 4, 5 & C available to 50 amps maximum.  
Terminal Codes 3, 6 & 9 available to 100 amps maximum.  
10 Terminal Code A available to 100 amps maximum.  
11 VDE and TUV approvals require Dual (I-O, ON-OFF) markings on all handles.  
12 Barriers supplied on multi-pole units only.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
|
10 C-Series Circuit Breaker - Sealed Toggle UL Recognized – Ordering Scheme  
C M 3 B 0 10 450 1 0 1 C  
8
9
10  
11  
Agency  
Approval  
1
2
3
4
5
6
7
Terminal  
Legend  
Plate  
Mounting  
Bezel/Barrier  
Series  
Actuator  
Poles  
Circuit  
Aux/Alarm  
Switch  
Frequency  
& Delay  
Current Rating  
9
1 SERIES  
C
7 CURRENT RATING (AMPERES)  
CODE AMPERES  
020 0.020  
025 0.025  
030 0.030  
035 0.035  
040 0.040  
045 0.045  
050 0.050  
055 0.055  
060 0.060  
065 0.065  
070 0.070  
075 0.075  
080 0.080  
085 0.085  
090 0.090  
095 0.095  
210 0.100  
215 0.150  
220 0.200  
225 0.250  
230 0.300  
235 0.350  
240 0.400  
245 0.450  
250 0.500  
255 0.550  
260 0.600  
265 0.650  
270 0.700  
275 0.750  
280 0.800  
285 0.850  
290 0.900  
295 0.950  
410 1.000  
512 1.250  
415 1.500  
517 1.750  
420 2.000  
522 2.250  
425 2.500  
527 2.750  
430 3.000  
614 14.000  
615 15.000  
616 16.000  
617 17.000  
618 18.000  
620 20.000  
622 22.000  
624 24.000  
625 25.000  
630 30.000  
635 35.000  
640 40.000  
650 50.000  
435 3.500  
440 4.000  
445 4.500  
450 5.000  
455 5.500  
460 6.000  
465 6.500  
470 7.000  
475 7.500  
480 8.000  
485 8.500  
490 9.000  
495 9.500  
610 10.000  
710 10.500  
611 11.000  
711 11.500  
612 12.000  
712 12.500  
613 13.000  
1
2 ACTUATOR  
M
Sealed Toggle, one per pole  
3 POLES  
1
One  
2
Two  
3
Three  
3
3
3,4  
4 CIRCUIT  
F
G
H
Relay Trip (current)  
Relay Trip (voltage)  
Dual Coil with Shunt Trip  
Voltage Coil  
Dual Coil with Relay Trip  
Voltage Coil  
2
A
B
C
D
E
Switch Only (no coil)  
9
Series Trip (current)  
Series Trip (voltage)  
Shunt Trip (current)  
Shunt Trip (voltage)  
660 60.000  
9
670 70.000  
9
3
3
3,4  
680 80.000  
K
9
685 85.000  
9
690 90.000  
9
695 95.000  
9
810 100.00  
5 AUXILIARY / ALARM SWITCH  
0
2
3
4
without Aux Switch  
7
OR VOLTAGE COIL (NORMAL RATED VOLTAGE)  
S.P.D.T., 0.110 Q.C. Term.  
S.P.D.T., 0.139 Solder Lug  
S.P.D.T., 0.110 Q.C. Term.  
(Gold Contacts)  
6
8
9
S.P.S.T., 0.139 Solder Lug  
S.P.S.T., 0.187 Q.C. Term.  
S.P.D.T., 0.187 Q.C. Term.  
CODE AMPERES  
A06  
6 DC  
A32 32 DC  
A48 48 DC  
A65 65 DC  
J12 12 AC  
J18 18 AC  
J24 24 AC  
J48 48 AC  
J65  
65 AC  
A12 12 DC  
A18 18 DC  
A24 24 DC  
K20 120 AC  
L40 240 AC  
J06  
6 AC  
6 FREQUENCY & DELAY  
2
8 TERMINAL  
03  
10  
11  
12  
14  
16  
20  
21  
22  
24  
26  
DC 50/60Hz, Switch Only  
DC Instantaneous  
DC Ultra Short  
DC Short  
DC Medium  
DC Long  
50/60Hz Instantaneous  
50/60Hz Ultra Short  
50/60Hz Short  
50/60Hz Medium  
50/60Hz Long  
30  
31  
32  
34  
36  
42  
44  
46  
52  
54  
56  
DC 50/60Hz Instantaneous  
DC 50/60Hz Ultra Short  
DC 50/60Hz Short  
DC 50/60Hz Medium  
DC 50/60Hz Long  
50/60Hz Short, Hi-Inrush  
50/60Hz Medium, Hi-Inrush  
50/60Hz Long, Hi-Inrush  
DC Short, Hi-Inrush  
DC Medium, Hi-Inrush  
DC Long, Hi-Inrush  
9
11  
6
1
2
3
4
5
Stud 10-32  
Screw 10-32  
Stud 1/4-20  
Stud M5 x 0.8  
Screw M5 x 0.8  
6
7
9
A
C
Stud M6  
10  
11  
10  
10  
12  
11  
13  
10  
0.250 Double Click Connect  
7/16” Clip Terminal  
Plug-In Stud  
7
7
7
7
5/16” Clip Terminal  
6
9 LEGEND PLATE  
No Legend  
7
0
10 MOUNTING / BARRIERS  
MOUNTING STYLE  
Notes:  
1
Actuator Code M: Handle location as viewed from front of breaker:  
2 pole - right pole 3 pole - center pole  
Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE.  
For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current  
Code 650. For 55-70 amps, select Current Code 670. For 75-100 amps, select  
Current Code 810.  
BARRIERS  
no  
yes  
1
A
Standard Hex Nut  
Standard Hex Nut (multi-pole units only)  
2
11 AGENCY APPROVAL  
3
4
Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only.  
Consult factory for available Dual Coil options, as special catalog number is  
required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously  
on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip  
instantaneously and are rated for intermittent duty only.  
C
I
L
UL Recognized & CSA Accepted  
UL Recognized & CSA Accepted, UL1500 ignition protection  
UL Recognized & CSA Accepted with listed construction  
5
Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole  
breakers, one auxiliary switch is supplied, mounted in the extreme right pole.  
Voltage coils not rated for continuous duty. Available only with delay codes 10 & 20.  
Available with Circuit Codes B & D only, and up to 50 amps maximum.  
Consult factory for current ratings 71-100, in three pole units, available as special  
catalog number only.  
6
7
8
9
Terminal Code 1 available to 60 amps maximum.  
10 Terminal Codes 2, 4, 5 and C available to 50 amps maximum.  
11 Terminal Codes 3, 6 & 9 available to 100 amps maximum.  
12 Terminal Code 7 available to 25 amps maximum.  
13 Terminal Code A available to 100 amps maximum.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
C-Series Circuit Breaker - Rocker UL Recognized – Ordering Scheme |  
11  
14 450  
C C 3 B 0  
1 2 1 D  
6
7
8
9
10  
Mounting/  
Barriers  
11  
Agency  
Approval  
1
2
3
4
5
Frequency  
& Delay  
Current Rating  
Terminal  
Actuator  
Color  
Series  
Actuator  
Poles  
Circuit  
Aux/Alarm  
Switch  
1 SERIES  
C
7 CURRENT RATING (AMPERES)  
CODE AMPERES  
020 0.020  
025 0.025  
030 0.030  
035 0.035  
040 0.040  
045 0.045  
050 0.050  
055 0.055  
060 0.060  
065 0.065  
070 0.070  
075 0.075  
080 0.080  
085 0.085  
090 0.090  
095 0.095  
210 0.100  
215 0.150  
220 0.200  
225 0.250  
230 0.300  
235 0.350  
240 0.400  
245 0.450  
250 0.500  
255 0.550  
260 0.600  
265 0.650  
270 0.700  
275 0.750  
280 0.800  
285 0.850  
290 0.900  
295 0.950  
410 1.000  
512 1.250  
415 1.500  
517 1.750  
420 2.000  
522 2.250  
425 2.500  
527 2.750  
430 3.000  
435 3.500  
440 4.000  
445 4.500  
450 5.000  
455 5.500  
460 6.000  
465 6.500  
470 7.000  
475 7.500  
480 8.000  
485 8.500  
490 9.000  
495 9.500  
610 10.000  
710 10.500  
611 11.000  
711 11.500  
612 12.000  
712 12.500  
613 13.000  
614 14.000  
615 15.000  
616 16.000  
617 17.000  
618 18.000  
620 20.000  
622 22.000  
624 24.000  
625 25.000  
630 30.000  
635 35.000  
640 40.000  
650 50.000  
1
2 ACTUATOR  
Two Color Visi-Rocker  
C
D
E
F
Indicate ON, vertical legend  
Indicate ON, horizontal legend  
Indicate ON, no legend  
Indicate OFF, vertical legend  
Indicate OFF, horizontal legend  
Indicate OFF, no legend  
G
H
Push-To-Reset, Visi-Rocker  
N
O
P
Indicate OFF, vertical legend  
Indicate OFF, horizontal legend  
Indicate OFF, no legend  
9
660 60.000  
9
Single color  
670 70.000  
9
J
K
L
Vertical legend  
Horizontal legend  
No legend  
680 80.000  
9
685 85.000  
9
690 90.000  
9
Push-To-Reset, Single color  
695 95.000  
9
R
U
V
Vertical legend  
Horizontal legend  
No legend  
810 100.00  
7
OR VOLTAGE COIL (NORMAL RATED VOLTAGE)  
CODE AMPERES  
A06  
6 DC  
A32 32 DC  
A48 48 DC  
A65 65 DC  
J12 12 AC  
J18 18 AC  
J24 24 AC  
J48 48 AC  
J65  
65 AC  
A12 12 DC  
A18 18 DC  
A24 24 DC  
K20 120 AC  
L40 240 AC  
2
3 POLES  
One  
1
2
Two  
3
Three  
J06  
6 AC  
4
4
4,5  
4,5  
4 CIRCUIT  
F
Relay Trip (Current)  
Relay Trip (Voltage)  
3
8 TERMINAL  
A
B
C
D
E
Switch Only (No Coil)  
G
H
10  
12  
13  
1
2
3
4
5
Stud 10-32  
6
Stud M6  
Series Trip (Current)  
Series Trip (Voltage)  
Shunt Trip (Current)  
Shunt Trip (Voltage)  
Dual Coil with Shunt Trip  
Voltage Coil  
11  
12  
11  
11  
Screw 10-32  
Stud 1/4-20  
7
0.250 Double Quick Connect  
7/16” Clip Terminal  
Plug-In Stud  
4
4
9
A
C
K
Dual Coil with Relay Trip  
Voltage Coil  
14  
Stud M5 x 0.8  
Screw M5 x 0.8  
5/16” Clip Terminal  
6
5 AUXILIARY / ALARM SWITCH  
16,17,18  
9 ACTUATOR COLOR & LEGEND  
Actuator or  
0
2
3
4
without Aux Switch  
S.P.D.T., 0.110 Q.C. Term.  
S.P.D.T., 0.139 Solder Lug  
S.P.D.T., 0.110 Q.C. Term.  
(Gold Contacts)  
6
8
9
S.P.S.T., 0.139 Solder Lug  
S.P.S.T., 0.187 Q.C. Term.  
S.P.D.T., 0.187 Q.C. Term.  
Visi-Color Marking:  
MarkingColor:  
Single Color  
Color:  
White  
Black  
Red  
I-O ON-OFF Dual/None Rocker/Handle Visi-Rocker  
A
C
F
H
K
M
P
R
B
D
G
J
1
2
3
4
5
6
7
8
Black  
White  
White  
White  
White  
Black  
Black  
Black  
White  
n/a  
Red  
6 FREQUENCY & DELAY  
Green  
Blue  
Green  
Blue  
Yellow  
Gray  
Orange  
03  
10  
11  
12  
14  
16  
20  
21  
22  
24  
26  
DC 50/60Hz, Switch Only  
DC Instantaneous  
DC Ultra Short  
DC Short  
30  
DC 50/60Hz Instantaneous  
DC 50/60Hz Ultra Short  
DC 50/60Hz Short  
L
7
31  
32  
34  
36  
42  
44  
46  
52  
54  
56  
Yellow  
Gray  
Orange  
N
Q
S
DC 50/60Hz Medium  
DC 50/60Hz Long  
DC Medium  
8
8
8
8
8
8
DC Long  
50/60Hz Short, Hi-Inrush  
7
1
50/60Hz Instantaneous  
50/60Hz Ultra Short  
50/60Hz Short  
50/60Hz Medium, Hi-Inrush  
10 MOUNTING / BARRIERS  
50/60Hz Long, Hi-Inrush  
STANDARD ROCKER BEZEL  
6-32 x 0.195 inches  
6-32 x 0.195 inches  
ꢀꢀ 6-32ꢀxꢀ0.195ꢀinchesꢀ  
ISO M3 x 5mm  
BARRIERS  
VOLTAGE  
<300  
DC Short, Hi-Inrush  
1
2
3
4
5
6
no  
50/60Hz Medium  
50/60Hz Long  
DC Medium, Hi-Inrush  
yes  
yesꢀ  
no  
yes  
yesꢀ  
<300  
19  
19  
DC Long, Hi-Inrush  
≥300  
<300  
Notes:  
ISO M3 x 5mm  
<300  
1
2
Push-To-Reset actuators have OFF portion of rocker shrouded.  
ꢀꢀ ISOꢀM3ꢀxꢀ5mmꢀ  
≥300  
Multi-pole breakers have all poles identical except when specifying Auxiliary switch  
and/or mixed poles, and have one rocker per breaker. Rocker location as viewed from  
front panel: 2 pole – left pole; 3 pole – center pole.  
ROCKERGUARD BEZEL  
6-32 x 0.195 inches  
6-32 x 0.195 inches  
ꢀꢀ 6-32ꢀxꢀ0.195ꢀinchesꢀ  
ISO M3 x 5mm  
ISO M3 x 5mm  
A
C
E
G
J
no  
<300  
<300  
≥300  
<300  
<300  
≥300  
3
Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE  
Certificationꢀwhenꢀtiedꢀtoꢀaꢀprotectedꢀpoleꢀ(CircuitꢀCodeꢀB,ꢀC,ꢀDꢀorꢀH.),ꢀForꢀ.02ꢀtoꢀꢀ  
30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650.  
For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810.  
Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit  
Codes D,F,H & K available up to 50 amps maximum Current Rating.  
Consult factory for available Dual Coil options, as special catalog number is  
required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously  
on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip  
instantaneously and are rated for intermittent duty only.  
yes  
yesꢀ  
no  
19  
19  
4
5
yes  
yesꢀ  
L
ꢀꢀ ISOꢀM3ꢀxꢀ5mmꢀ  
PUSH-TO-RESET BEZEL  
6-32 x 0.195 inches  
6-32 x 0.195 inches  
ꢀꢀ 6-32ꢀxꢀ0.195ꢀinchesꢀ  
ISO M3 x 5mm  
B
D
F
H
J
M
no  
<300  
<300  
≥300  
<300  
<300  
≥300  
yes  
yesꢀ  
no  
19  
6
Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole  
breakers, one auxiliary switch is supplied, mounted in the extreme right pole. Auxiliary  
switch codes 2, 3 & 4 are VDE approved.  
ISO M3 x 5mm  
ꢀꢀ ISOꢀM3ꢀxꢀ5mmꢀ  
yes  
yesꢀ  
7
8
9
Voltage coils not rated for continuous duty. Available only with delay codes 10 & 20.  
Available with Circuit Codes B & D only, and up to 50 amps maximum.  
Current Ratings 60-70 are available up to four poles maximum. Ratings 71-100 are  
available up to two poles maximum.  
19  
10 Terminal Code 1 available to 60 amps maximum.  
11 AGENCY APPROVAL  
UL Recognized & CSA Accepted  
11 Terminal Codes 2,4,5 & C available to 50 amps maximum.  
12 Terminal Codes 3,6 & 9 available to 100 amps maximum.  
13 Terminal Code 7 available to 25 amps maximum.  
C
Dꢀꢀ VDEꢀCertified,ꢀULꢀRecognizedꢀ&ꢀCSAꢀAccepted  
Eꢀꢀ TUVꢀCertified,ꢀULꢀRecognizedꢀ&ꢀCSAꢀAccepted  
14 Terminal Code A available to 100 amps maximum.  
15 Terminal Codes 7, 9 & C are not VDE approved.  
Hꢀꢀ UL489ꢀConstruction:ꢀVDEꢀCertified,ꢀULꢀRecognizedꢀ&ꢀCSAꢀAccepted  
16 Color shown is visi and legend with remainder of rocker black  
17 Legend on Push-to-reset bezel/shroud is white when single color rocker is ordered.  
Dual = ON-OFF/I-O legend with actuator codes C - G, and J, K, N, O, R, & U. None  
= no legend with actuator codes H, L, P, V. Rockerguard available with actuator  
codes C - L. Push-to-reset available with actuator codes N, O, P, R, U, V.  
18 VDE/TUV approval requires Dual (I-O, ON-OFF) or I-O markings on rocker.  
19 VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 - 4 poles only  
and limited to AC Delays. “General Purpose amps” not rated for “full load amps” or  
to be used in applications with a motor.  
I
UL Recognized STD 1077, UL Recognized 1500 (ignition protected),  
& CSA Accepted  
L
Rꢀ  
UL489 Construction: UL Recognized & CSA Accepted  
UL489ꢀConstruction:ꢀTUVꢀCertified,ꢀULꢀRecognizedꢀ&ꢀCSAꢀAccepted  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
|
12 C-Series Circuit Breaker - Rocker UL Listed – Ordering Scheme  
C C 3 B 0 14 450 1 2 A K G  
8
9
10  
Mounting/  
Barriers  
11  
12  
1
2
3
4
5
6
7
Terminal  
Actuator  
Color  
Max. App. Agency  
Series  
Actuator  
Poles  
Circuit  
Aux/Alarm  
Switch  
Frequency  
& Delay  
Current Rating  
Rating  
Approval  
4
7 CURRENT RATING (AMPERES)  
1 SERIES  
C
CODE AMPERES  
210 0.100  
215 0.150  
220 0.200  
225 0.250  
230 0.300  
235 0.350  
240 0.400  
245 0.450  
250 0.500  
255 0.550  
260 0.600  
265 0.650  
270 0.700  
275 0.750  
280 0.800  
285 0.850  
290 0.900  
295 0.950  
410 1.000  
512 1.250  
415 1.500  
517 1.750  
420 2.000  
522 2.250  
425 2.500  
527 2.750  
430 3.000  
435 3.500  
440 4.000  
445 4.500  
450 5.000  
455 5.500  
460 6.000  
465 6.500  
470 7.000  
475 7.500  
480 8.000  
485 8.500  
490 9.000  
495 9.500  
610 10.000  
710 10.500  
611 11.000  
711 11.500  
612 12.000  
712 12.500  
613 13.000  
614 14.000  
615 15.000  
616 16.000  
617 17.000  
618 18.000  
620 20.000  
622 22.000  
624 24.000  
625 25.000  
630 30.000  
635 35.000  
640 40.000  
650 50.000  
660 60.000  
670 70.000  
680 80.000  
685 85.000  
690 90.000  
695 95.000  
810 100.00  
1
2 ACTUATOR  
Two Color Visi-Rocker  
Single color  
C
D
F
Indicate ON, vertical legend  
Indicate ON, horizontal legend  
Indicate OFF, vertical legend  
J
K
Vertical legend  
Horizontal legend  
G
Indicate OFF, horizontal legend  
ROCKER STYLE DESCRIPTIONS  
INDICATE "ON"  
INDICATE "OFF"  
CODE "F"  
SINGLE COLOR  
CODE "J"  
CODE "C"  
LINE  
INDICATE  
COLOR  
LINE  
LINE  
LOCATION  
CODE "D"  
CODE "G"  
CODE "K"  
8 TERMINAL  
5
7
1
2
Stud 10-32  
6
9
A
C
Stud M6  
7/16” Clip Terminal  
Plug-In Stud  
6
7,8  
7,8  
6,8  
Screw 10-32 with saddle  
& washer clamps  
Stud 1/4-20  
7
6
6
3
4
5
5/16” Clip Terminal  
LINE  
LINE  
LINE  
Stud M5 x 0.8  
Screw M5 x 0.8 with saddle  
& washer clamps  
1
3 POLES  
One  
1
2
Two  
3
Three  
11  
9 ACTUATOR COLOR & LEGEND  
Actuator or  
4 CIRCUIT  
Series Trip (current)  
Visi-Color  
Marking:  
Marking Color:  
Single Color  
Rocker/Handle  
Black  
B
10  
Color:  
White  
Black  
Red  
ON-OFF Dual  
Visi-Rocker  
White  
n/a  
B
D
G
J
1
2
3
4
5
6
7
8
2
5 AUXILIARY / ALARM SWITCH  
White  
0
2
3
4
without Aux Switch  
White  
Red  
S.P.D.T., 0.110 Q.C. Term.  
S.P.D.T., 0.139 Solder Lug  
S.P.D.T., 0.110 Q.C. Term.  
(Gold Contacts)  
6
8
9
S.P.S.T., 0.139 Solder Lug  
S.P.S.T., 0.187 Q.C. Term.  
S.P.D.T., 0.187 Q.C. Term.  
Green  
Blue  
White  
Green  
Blue  
L
White  
Yellow  
Gray  
Orange  
N
Q
S
Black  
Yellow  
Gray  
Black  
Black  
Orange  
6 FREQUENCY & DELAY  
11 DC Ultra Short  
12 DC Short  
14 DC Medium  
16 DC Long  
21 50/60Hz Ultra Short  
22 50/60Hz Short  
24 50/60Hz Medium  
26 50/60Hz Long  
8
8
8
8
12  
42 50/60Hz Short, Hi-Inrush  
10 MOUNTING / BARRIERS  
Standard Rocker Bezel  
13  
44 50/60Hz Medium, Hi-Inrush  
BARRIERS  
46 50/60Hz Long, Hi-Inrush  
Threaded Insert, 2 per pole  
6-32 X 0.195 inches  
ISO M3 x 5mm  
Rockerguard Bezel  
Threaded Insert, 2 per pole  
6-32 x 0.195 inches  
ISO M3 x 5mm  
52 DC Short, Hi-Inrush  
A
C
yes  
yes  
8
54 DC Medium, Hi-Inrush  
56 DC Long, Hi-Inrush  
B
D
yes  
yes  
Notes:  
1
Multi-pole breakers have all breakers identical except when specifying Auxiliary  
switch and/or mixed poles, and have one rocker per breaker.  
On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right  
pole.  
11 MAXIMUM APPLICATION RATING  
2
A
B
C
D
F
K
M
65 DC  
125 DC  
120/240 AC  
240 AC  
277 AC  
120 AC  
80 DC  
3
4
5
6
7
8
9
Available up to 50 amps maximum.  
14  
Current ratings 71 - 100 with VDE approvals are available up to two poles maximum.  
Terminal Code 1 available to 60 amps maximum.  
Terminal Codes 2, 4, 5 & C available to 50 amps maximum.  
Terminal Codes 3, 6, 9 & A available to 100 amps maximum.  
Terminal Codes 9 & C are not VDE approved.  
Color shown is visi and legend with remainder of rocker black  
10 Dual = ON-OFF/I-O legend on actuator.  
11 VDE and TUV approval requires Dual (I-O, ON-OFF) markings on rocker.  
12 Rockerguard available with all actuator codes.  
12 AGENCY APPROVAL  
13 Barriers supplied on multi-pole units only.  
A
Fꢀꢀ  
G
without approvals  
ULꢀ489ꢀListed,ꢀCSAꢀCertified,ꢀ&ꢀVDEꢀCertified  
ULꢀ489ꢀListedꢀ&ꢀCSAꢀCertified  
14 2 & 3 pole circuit breakers required for 120/240 AC rating.  
Jꢀꢀ  
UL489ꢀListed,ꢀCSAꢀCertifiedꢀ&ꢀTUVꢀCertified  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
C-Series Circuit Breaker - Flat Rocker UL Recognized – Ordering Scheme |  
13  
C 1 2 B 0 10 450 1 2 1 E  
8
9
10  
Mounting/  
Barriers  
11  
Agency  
Approval  
1
2
3
4
5
6
7
Terminal  
Actuator  
Color  
Series  
Actuator  
Poles  
Circuit  
Aux/Alarm  
Switch  
Frequency  
& Delay  
Current Rating  
9
1 SERIES  
C
7 CURRENT RATING (AMPERES)  
CODE AMPERES  
020 0.020  
025 0.025  
030 0.030  
035 0.035  
040 0.040  
045 0.045  
050 0.050  
055 0.055  
060 0.060  
065 0.065  
070 0.070  
075 0.075  
080 0.080  
085 0.085  
090 0.090  
095 0.095  
210 0.100  
215 0.150  
220 0.200  
225 0.250  
230 0.300  
235 0.350  
240 0.400  
245 0.450  
250 0.500  
255 0.550  
260 0.600  
265 0.650  
270 0.700  
275 0.750  
280 0.800  
285 0.850  
290 0.900  
295 0.950  
410 1.000  
512 1.250  
415 1.500  
517 1.750  
420 2.000  
522 2.250  
425 2.500  
527 2.750  
430 3.000  
435 3.500  
440 4.000  
445 4.500  
450 5.000  
455 5.500  
460 6.000  
465 6.500  
470 7.000  
475 7.500  
480 8.000  
485 8.500  
490 9.000  
495 9.500  
610 10.000  
710 10.500  
611 11.000  
711 11.500  
612 12.000  
712 12.500  
613 13.000  
614 14.000  
615 15.000  
616 16.000  
617 17.000  
618 18.000  
620 20.000  
622 22.000  
624 24.000  
625 25.000  
630 30.000  
635 35.000  
640 40.000  
650 50.000  
1
2 ACTUATOR  
Two Color Visi-Rocker  
1
Indicate OFF,  
vertical legend  
Indicate OFF,  
horizontal legend  
2
Single color  
3
4
Vertical legend  
Horizontal legend  
Push-To-Reset, Visi-Rocker  
5
Indicate OFF,  
vertical legend  
Indicate OFF,  
9
660 60.000  
9
670 70.000  
6
9
680 80.000  
horizontal legend  
9
685 85.000  
Push-To-Reset , Single color  
9
690 90.000  
7
8
Vertical legend  
9
695 95.000  
Horizontal legend  
9
810 100.00  
7
OR VOLTAGE COIL (NORMAL RATED VOLTAGE)  
2
3 POLES  
One  
CODE AMPERES  
1
2
Two  
3
Three  
A06  
6 DC  
A32 32 DC  
A48 48 DC  
A65 65 DC  
J12 12 AC  
J18 18 AC  
J24 24 AC  
J48 48 AC  
J65  
65 AC  
A12 12 DC  
A18 18 DC  
A24 24 DC  
K20 120 AC  
L40 240 AC  
4
4
4,5  
4,5  
4 CIRCUIT  
F
Relay Trip (Current)  
Relay Trip (Voltage)  
J06  
6 AC  
3
A
B
C
D
E
Switch Only (No Coil)  
G
H
Series Trip (Current)  
Series Trip (Voltage)  
Shunt Trip (Current)  
Shunt Trip (Voltage)  
Dual Coil with Shunt Trip  
Voltage Coil  
8 TERMINAL  
4
4
K
Dual Coil with Relay Trip  
Voltage Coil  
10  
12  
1
2
3
4
5
Stud 10-32  
6
Stud M6  
11  
12  
11  
11  
13  
15  
14  
15  
Screw 10-32  
Stud 1/4-20  
7
0.250 Double Quick Connect  
7/16” Clip Terminal  
Plug-In Stud  
9
Stud M5 x 0.8  
Screw M5 x 0.8  
A
C
6
5 AUXILIARY / ALARM SWITCH  
5/16” Clip Terminal  
0
2
3
4
without Aux Switch  
S.P.D.T., 0.110 Q.C. Term.  
S.P.D.T., 0.139 Solder Lug  
S.P.D.T., 0.110 Q.C. Term.  
(Gold Contacts)  
6
8
9
S.P.S.T., 0.139 Solder Lug  
S.P.S.T., 0.187 Q.C. Term.  
S.P.D.T., 0.187 Q.C. Term.  
16,17,18  
9 ACTUATOR COLOR & LEGEND  
Actuator or  
Visi-Color Marking:  
MarkingColor:  
Single Color  
Color:  
White  
Black  
Red  
I-O ON-OFF Dual/None Rocker/Handle Visi-Rocker  
A
C
F
B
D
G
J
1
2
3
4
5
6
7
8
Black  
White  
White  
White  
White  
Black  
Black  
Black  
White  
n/a  
6 FREQUENCY & DELAY  
03  
10  
11  
12  
14  
16  
20  
21  
22  
24  
26  
DC 50/60Hz, Switch Only  
DC Instantaneous  
DC Ultra Short  
DC Short  
30  
DC 50/60Hz Instantaneous  
DC 50/60Hz Ultra Short  
DC 50/60Hz Short  
7
Red  
31  
32  
34  
36  
42  
44  
46  
52  
54  
56  
Green  
Blue  
H
K
M
P
R
Green  
Blue  
L
DC 50/60Hz Medium  
DC 50/60Hz Long  
Yellow  
Gray  
N
Q
S
Yellow  
Gray  
Orange  
DC Medium  
DC Long  
8
8
8
8
8
8
50/60Hz Short, Hi-Inrush  
7
Orange  
50/60Hz Instantaneous  
50/60Hz Ultra Short  
50/60Hz Short  
50/60Hz Medium, Hi-Inrush  
50/60Hz Long, Hi-Inrush  
DC Short, Hi-Inrush  
1
10 MOUNTING / BARRIERS  
50/60Hz Medium  
50/60Hz Long  
DC Medium, Hi-Inrush  
STANDARD ROCKER BEZEL  
6-32 x 0.195 inches  
6-32 x 0.195 inches  
ꢀꢀ 6-32ꢀxꢀ0.195ꢀinchesꢀ  
ISO M3 x 5mm  
BARRIERS  
no  
yes  
yesꢀ  
no  
yes  
yesꢀ  
VOLTAGE  
<300  
DC Long, Hi-Inrush  
1
2
3
4
5
6
<300  
Notes:  
19  
19  
≥300  
1
2
Push-to-reset actuators have OFF portion of rocker shrouded.  
Multi-pole breakers have all poles identical except when specifying Auxiliary switch  
and/or mixed poles, and have one rocker per breaker. Rocker location as viewed  
from front panel: 2 pole – left pole; 3 pole – center pole.  
<300  
ISO M3 x 5mm  
<300  
ꢀꢀ ISOꢀM3ꢀxꢀ5mmꢀ  
≥300  
3
Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE  
Certificationꢀwhenꢀtiedꢀtoꢀaꢀprotectedꢀpoleꢀ(CircuitꢀCodeꢀB,ꢀC,ꢀDꢀorꢀH.).ꢀForꢀ.02ꢀtoꢀ30ꢀꢀ  
amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. For  
55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810.  
Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit  
Codes D,F,H & K available up to 50 amps maximum Current Rating.  
Consult factory for available Dual Coil options, as special catalog number is required.  
Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously on line  
voltage. Dual Coil Voltage Coils require 30VA minimum power to trip instantaneously  
and are rated for intermittent duty only.  
RECESSED OFF ROCKER  
6-32 x 0.195 inches  
6-32 x 0.195 inches  
6-32ꢀxꢀ0.195ꢀinchesꢀꢀ  
ISO M3 x 5mm  
7
8
no  
<300  
<300  
≥300  
<300  
<300  
≥300  
yes  
yesꢀꢀ  
no  
4
5
9ꢀꢀ  
A
C
E ꢀ  
ISO M3 x 5mm  
yes  
yesꢀꢀ  
ISOꢀM3ꢀxꢀ5mmꢀꢀ  
PUSH-TO-RESET BEZEL  
6-32 x 0.195 inches  
6-32 x 0.195 inches  
6
Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole  
breakers, one auxiliary switch is supplied, mounted in the extreme right pole. Auxilary  
switch codes 2, 3 & 4 are VDE approved.  
B
D
F
H
J
no  
<300  
<300  
≥300  
<300  
<300  
≥300  
yes  
yesꢀ  
no  
19  
ꢀꢀ 6-32ꢀxꢀ0.195ꢀinchesꢀ  
ISO M3 x 5mm  
ISO M3 x 5mm  
ꢀꢀ ISOꢀM3ꢀxꢀ5mmꢀ  
7
8
9
Voltage coils not rated for continuous duty. Available only with delay codes 10 and 20.  
Available with Circuit Codes B & D only, and up to 50 amps maximum.  
Current ratings 60-70 are available up to four poles maximum. Current ratings 71 -  
100 are available up to two poles maximum.  
yes  
yesꢀ  
19  
M
10 Terminal Code 1 available to 60 amps maximum.  
11 Terminal Codes 2,4,5 & C available to 50 amps maximum.  
12 Terminal Codes 3,6 & 9 available to 100 amps maximum.  
13 Terminal Code 7 available to 25 amps maximum.  
11 AGENCY APPROVAL  
UL Recognized & CSA Accepted  
14 Terminal Code A available to 100 amps maximum.  
C
15 Terminal Codes 7, 9 & C are not VDE approved.  
Eꢀꢀ TUVꢀCertified,ꢀULꢀRecognizedꢀ&ꢀCSAꢀAccepted  
16 Color shown is visi & legend with remainder of rocker black. Dual = ON-OFF/I-O legend.  
17 Legend on Push-to-reset bezel/shroud is white with single color actuator codes 7 &  
8. Legend on Push-to-reset bezel/shroud matches visi-color of rocker with actuator  
codes 5 & 6.  
I
UL Recognized STD 1077, UL Recognized 1500 (ignition protected),  
& CSA Accepted  
UL489 Construction: UL Recognized & CSA Accepted  
UL489ꢀConstruction:ꢀTUVꢀCertified,ꢀULꢀRecognizedꢀ&ꢀCSAꢀAccepted  
L
18 VDE/TUV approval requires Dual (I-O, ON-OFF) or I-O markings on rocker.  
19 VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 & 3 poles only and  
limited to AC Delays. “General Purpose amps” not rated for “full load amps” or to be  
used in applications with a motor.  
20 Recessed “OFF SIDE” available with actuator codes 1,2,3&4. Legends on rocker are  
available in ink stamping only.  
Rꢀ  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
|
14 C-Series Circuit Breaker - Flat Rocker UL Listed – Ordering Scheme  
C 1 2 B 0 14 450 1 2 A K G  
8
9
10  
Mounting/  
Barriers  
11  
12  
1
2
3
4
5
6
7
Terminal  
Actuator  
Color  
Max. App. Agency  
Series  
Actuator  
Poles  
Circuit  
Aux/Alarm  
Switch  
Frequency  
& Delay  
Current Rating  
Rating  
Approval  
5
7 CURRENT RATING (AMPERES)  
1 SERIES  
C
CODE AMPERES  
210 0.100  
215 0.150  
220 0.200  
225 0.250  
230 0.300  
235 0.350  
240 0.400  
245 0.450  
250 0.500  
255 0.550  
260 0.600  
265 0.650  
270 0.700  
275 0.750  
280 0.800  
285 0.850  
290 0.900  
295 0.950  
410 1.000  
512 1.250  
415 1.500  
517 1.750  
420 2.000  
522 2.250  
425 2.500  
527 2.750  
430 3.000  
435 3.500  
440 4.000  
445 4.500  
450 5.000  
455 5.500  
460 6.000  
465 6.500  
470 7.000  
475 7.500  
480 8.000  
485 8.500  
490 9.000  
495 9.500  
610 10.000  
710 10.500  
611 11.000  
711 11.500  
612 12.000  
712 12.500  
613 13.000  
614 14.000  
615 15.000  
616 16.000  
617 17.000  
618 18.000  
620 20.000  
622 22.000  
624 24.000  
625 25.000  
630 30.000  
635 35.000  
640 40.000  
650 50.000  
660 60.000  
670 70.000  
680 80.000  
685 85.000  
690 90.000  
695 95.000  
810 100.00  
1
2 ACTUATOR  
Two Color Visi-Rocker  
Push-To-Reset, Visi-Rocker  
1
2
Indicate OFF, vertical legend  
Indicate OFF, horizontal legend  
5
6
Indicate OFF, vertical legend  
Indicate OFF, horizontal legend  
Single color  
3
4
Push-To-Reset , Single color  
Vertical legend  
Horizontal legend  
7
8
Vertical legend  
Horizontal legend  
8 TERMINAL  
6
8
8,9  
8
1
2
3
4
5
Stud 10-32  
6
9
A
C
Stud M6  
7/16” Clip Terminal  
Plug-In Stud  
7
8
7
7
Screw 10-32  
Stud 1/4-20  
Stud M5 x 0.8  
7,9  
5/16” Clip Terminal  
Screw M5 x 0.8  
10  
9 ACTUATOR COLOR & LEGEND  
2
3 POLES  
One  
Actuator or  
1
2
Two  
3
Three  
Visi-Color  
Marking:  
Marking Color:  
Single Color  
Rocker/Handle  
Black  
11,12  
Color:  
White  
Black  
Red  
ON-OFF Dual  
Visi-Rocker  
White  
n/a  
4 CIRCUIT  
Series Trip (current)  
B
D
G
J
1
2
3
4
5
6
7
8
B
White  
White  
Red  
Green  
Blue  
White  
Green  
Blue  
3
5 AUXILIARY / ALARM SWITCH  
L
White  
Yellow  
Gray  
Orange  
N
Q
S
Black  
Yellow  
Gray  
0
2
3
4
without Aux Switch  
Black  
S.P.D.T., 0.110 Q.C. Term.  
S.P.D.T., 0.139 Solder Lug  
S.P.D.T., 0.110 Q.C. Term.  
(Gold Contacts)  
6
8
9
S.P.S.T., 0.139 Solder Lug  
S.P.S.T., 0.187 Q.C. Term.  
S.P.D.T., 0.187 Q.C. Term.  
Black  
Orange  
10 MOUNTING / BARRIERS  
15  
STANDARD ROCKER BEZEL  
Threaded Insert, 2 per pole  
6-32 X 0.195 inches  
BARRIERS  
6 FREQUENCY & DELAY  
11 DC Ultra Short  
12 DC Short  
14 DC Medium  
16 DC Long  
21 50/60Hz Ultra Short  
22 50/60Hz Short  
24 50/60Hz Medium  
26 50/60Hz Long  
4
4
4
4
4
4
A
C
yes  
yes  
42 50/60Hz Short, Hi-Inrush  
44 50/60Hz Medium, Hi-Inrush  
46 50/60Hz Long, Hi-Inrush  
52 DC Short, Hi-Inrush  
54 DC Medium, Hi-Inrush  
56 DC Long, Hi-Inrush  
ISO M3 x 5mm  
14  
RECESSED OFF ROCKER  
Threaded Insert, 2 per pole  
6-32 x 0.195 inches  
ISO M3 x 5mm  
E
F
yes  
yes  
13  
PUSH-TO-RESET BEZEL  
Threaded Insert, 2 per pole  
6-32 x 0.195 inches  
ISO M3 x 5mm  
B
D
yes  
yes  
Notes:  
1
2
Push-to-reset actuators have OFF portion of rocker shrouded.  
Multi-pole breakers have all breakers identical except when specifying Auxiliary  
switch and/or mixed poles, and have one rocker per breaker.  
On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme  
right pole.  
11 MAXIMUM APPLICATION RATING  
3
A
B
C
D
F
K
M
65 DC  
4
5
6
7
8
9
Available up to 50 amps maximum.  
125 DC  
120/240 AC  
240 AC  
277 AC  
120 AC  
80 DC  
16  
Current ratings 71 - 100 with VDE approvals are available up to two poles maximum.  
Terminal Code 1 available to 60 amps maximum.  
Terminal Codes 2, 4, 5 & C available to 50 amps maximum.  
Terminal Codes 3, 6, 9 & A available to 100 amps maximum.  
Terminal Codes 9 & C are not VDE approved.  
10 Color shown is visi and legend with remainder of rocker black  
11 Dual = ON-OFF/I-O legend on actuator.  
12 TUV approval requires Dual (I-O, ON-OFF) markings on rocker.  
13 Legend on push-to-reset bezel/shroud is white when single color rocker is ordered.  
Legend on push-to-reset bezel/shroud matches visi-color of rocker with actuator  
codes 5 & 6.  
14 Recessed “OFF-SIDE” available with actuator codes 1, 2, 3, & 4. Legends on rocker  
are available in ink stamping only.  
12  
12 AGENCY APPROVAL  
A
without approvals  
G
Jꢀꢀ  
ULꢀ489ꢀListedꢀ&ꢀCSAꢀCertified  
UL489ꢀListed,ꢀCSAꢀCertifiedꢀ&ꢀTUVꢀCertified  
15 Barriers supplied on multi-pole units only.  
16 2 & 3 pole circuit breakers required for 120/240 AC rating.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
C-Series Circuit Breaker - Handle – Circuit & Terminal Diagrams |  
15  
Circuit & Terminal Diagrams: in. [mm]  
.960 [24.38]  
.311 DIA [Ø7.90]  
.558 [14.17]  
Notes:  
1
2
3
All dimensions are in inches [millimeters].  
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.  
Available on Series Trip and Switch Only Circuits when called for on multi-pole units.  
Onlyꢀoneꢀauxiliaryꢀswitchꢀisꢀnormallyꢀsupplied,ꢀasꢀviewedꢀinꢀmulit-poleꢀidentificationꢀscheme.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
|
16 C-Series Circuit Breaker - Handle – Circuit & Terminal Diagrams  
Circuit & Terminal Diagrams: in. [mm]  
Notes:  
1
2
3
4
All dimensions are in inches [millimeters].  
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.  
Schematic shown represents current trip circuits.  
Available only as special catalog number.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
C-Series Circuit Breaker - Handle – Dimensional Specifications |  
17  
Dimensional Specifications: in. [mm]  
Notes:  
1
2
All dimensions are in inches [millimeters].  
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
|
18 C-Series Circuit Breaker - Handleguard – Dimensional Specifications  
Dimensional Specifications: in. [mm]  
Notes:  
1
2
All dimensions are in inches [millimeters].  
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
C-Series Circuit Breaker - Arc Chute Barrier UL Recognized/Listed – Dimensional Specifications |  
19  
Dimensional Specifications: in. [mm]  
Notes:  
1
Onlyꢀ1-poleꢀandꢀ3-poleꢀconfigurationsꢀshown.ꢀArcꢀchuteꢀ(withoutꢀbarrier)ꢀandꢀarcꢀchuteꢀꢀ  
barrier also available for 2-pole construction.  
2
3
Dimensions apply to all variations shown.  
Notice that line and load terminal orientation for indicate on and indicate off rocker  
circuit breakers are opposite.  
4
5
6
7
Screw type terminals shown for Rocker style (CF1, C11, etc) circuit breakers. For  
otherꢀterminalꢀconfigurationsꢀseeꢀcircuitꢀandꢀterminalꢀdiagrams.  
All dimensions are in inches [millimeters].  
Toleranceꢀ±ꢀ.020ꢀunlessꢀotherwiseꢀspecified.  
Must be ordered under a special catalog number.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
|
20 C-Series Circuit Breaker - Parallel Pole – Dimensional Specifications  
Dimensional Specifications: in. [mm]  
Notes:  
1
2
All dimensions are in inches [millimeters].  
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
C-Series Circuit Breaker - Sealed Toggle – Dimensional Specifications |  
21  
Dimensional Specifications: in. [mm]  
Notes:  
1
2
All dimensions are in inches [millimeters].  
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
|
22 C-Series Circuit Breaker - Rocker – Circuit & Terminal Diagrams  
Circuit & Terminal Diagrams: in. [mm]  
Notes:  
1
2
3
All dimensions are in inches [millimeters].  
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.  
Schematic shown represents current trip circuit.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
C-Series Circuit Breaker - Rocker – Dimensional Specifications |  
23  
Dimensional Specifications: in. [mm]  
Notes:  
1
2
3
4
Dimensions apply to all variations shown. Notice that circuit breaker line and load terminal orientation on indicate OFF is opposite of indicate ON.  
For pole orientation with horizontal legend, rotate front view clockwise 90°.  
All dimensions are in inches [millimeters].  
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
|
24 C-Series Circuit Breaker - Flat Rocker – Dimensional Specifications  
Dimensional Specifications: in. [mm]  
Notes:  
1
2
3
For pole orientation with horizontal legend, rotate front view clockwise 90°.  
All dimensions are in inches [millimeters].  
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
|
Reps & Contact  
25  
Authorized Sales Representatives  
Click on the group name on the map below to find your local representative or visit  
www.carlingtech.com/findarep.  
Matera  
W. Canada  
Matera  
E. Canada  
MIDWEST  
DM  
MichigaNn ORTHERN  
TEMCO Northwest  
Hanna Lind Ltd.  
Melody  
Sierra  
Emery  
LD. Allen  
Norris  
«
DM Assoc  
Bridge Marketing  
Signal  
East  
Pacent  
TSI North  
Omega Limited  
Dy-tronix Inc.  
DM  
Assoc  
TSI  
Luscombe  
Engineering  
WEST  
Enterprises  
Pinnacle Marketing  
ProRep  
Sunbelt Components  
SOUTHEAST  
Matrix  
DM Mexico  
South America  
Mexico  
Solutions  
LATIN AMERICA  
Europe  
Middle East  
Africa  
Asia-Pacific  
Oceania  
Americas  
About Carling  
Founded in 1920, Carling Technologies is a leading manufacturer of electrical and electronic switches  
and assemblies, circuit breakers, electronic controls, power distribution units, and multiplexed power  
distribution systems. With four ISO registered manufacturing facilities and technical sales offices worldwide,  
Carling Technologies Sales, Service and Engineering teams do much more than manufacture electrical  
components, they engineer powerful solutions! To learn more about Carling please visit  
www.carlingtech.com/company-profile.  
To view all of Carling’s environmental, quality, health & safety certifications please visit  
www.carlingtech.com/environmental-certifications  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
Worldwide Headquarters  
Carling Technologies, Inc.  
60 Johnson Avenue, Plainville, CT 06062  
Phone: 860.793.9281 Fax: 860.793.9231  
@
Email: sales carlingtech.com  
@
Northern Region Sales Office: nrsm carlingtech.com  
@
Southeast Region Sales Office: sersm carlingtech.com  
@
Midwest Region Sales Office: mrsm carlingtech.com  
@
West Region Sales Office: wrsm carlingtech.com  
@
Latin America Sales Office: larsm carlingtech.com  
Asia-Pacific Headquarters  
Carling Technologies, Asia-Pacific Ltd.,  
Kowloon, Hong Kong  
Phone: Int + 852-2737-2277 Fax: Int + 852-2736-9332  
@
Email: sales carlingtech.com.hk  
@
Shenzhen, China: shenzhen carlingtech.com  
@
Shanghai, China: shanghai carlingtech.com  
@
Pune, India: india carlingtech.com  
@
Kaohsiung, Taiwan: taiwan carlingtech.com  
@
Yokohama, Japan: japan carlingtech.com  
|
|
Europe Middle East Africa Headquarters  
Carling Technologies LTD  
4 Airport Business Park, Exeter Airport,  
Clyst Honiton, Exeter, Devon, EX5 2UL, UK  
Phone: Int + 44 1392.364422 Fax: Int + 44 1392.364477  
@
Email: ltd.sales carlingtech.com  
@
Germany: gmbh carlingtech.com  
@
France: sas carlingtech.com  
www.carlingtech.com  
REV_07_2016  

相关型号:

CB2-B2-22-430-721-C

MAGNETIC CIRCUIT BREAKER,
Carling Techn

CB200-73

Toggle Switch, SPDT, Latched, Solder Terminal, Bat Type Actuator, Panel Mount-threaded,
Carling Techn

CB200-78

Toggle Switch, SPDT, Latched, Solder Terminal, Bat Type Actuator, Panel Mount-threaded
Carling Techn

CB2002

Wide Band Medium Power Amplifier, 800MHz Min, 950MHz Max,
APITECH

CB2003

Wide Band Medium Power Amplifier, 800MHz Min, 950MHz Max,
APITECH

CB2005

Wide Band Low Power Amplifier, 800MHz Min, 950MHz Max,
APITECH

CB2005

Fixed Resistor, Carbon Composition, 0.25W, 20ohm, 5% +/-Tol, Through Hole Mount, AXIAL LEADED
ALLEN-BRADLEY

CB2006

800 MHz - 950 MHz RF/MICROWAVE WIDE BAND LOW POWER AMPLIFIER
APITECH

CB2007

Wide Band Low Power Amplifier, 800MHz Min, 950MHz Max,
APITECH

CB2009

800 MHz - 950 MHz RF/MICROWAVE WIDE BAND MEDIUM POWER AMPLIFIER
APITECH

CB20110203

Barrier Strip Terminal Block, 30A, 1 Row(s), 1 Deck(s)
COOPER

CB20110203EB

30 A, BARRIER STRIP TERMINAL BLOCK, 1 ROW, 1 DECK
COOPER